Custom designed and fabricated multi-fuel boilers and heat plants.
Custom designed and fabricated multi-fuel boilers and heat plants.
Our boilers are available with a range of fuel options including biomass, solid fuel, gas, liquid fuel and electricity. Respected for our mechanical and project engineering capabilities, we provide comprehensive design, fabrication, installation, and commissioning services to a broad range of industry sectors.
Contact our sales expertsA corner tube boiler is a natural circulation water tube boiler. It differs from other water tube boilers in that it has the characteristics of a water-steam cycle. The pre-separation of heating steam and steam-water mixture occurs outside the drum in an unheated downcomer. This type of boiler is called a corner tube boiler.
Boiler model | DZS25 | DZS30 | DZS35 | DZS40 | DZS50 | |
Rated evaporation capacity (t/h) | 25 | 30 | 35 | 40 | 50 | |
Rated working pressure (MPa) | 1.25/1.6/2.5/3.82 | |||||
Saturated steam temperature(℃) | 194/204/226/250 | |||||
Superheated steam temperature (℃) | ≤450 | |||||
Rated feed water temperature (℃) | 104 | |||||
Full water capacity (m³) | 16.7 | 20.2 | 21.6 | 22.3 | 27.5 | |
Design thermal efficiency (%) | ≥99 | ≥99 | ≥99 | ≥99 | ≥99 | |
Exhaust smoke temperature (℃) | ≤70 | ≤70 | ≤70 | ≤70 | ≤70 | |
Design fuel | Natural gas, local city gas, gas, coke oven gas, 0# light diesel oil, etc. | |||||
Maximum shipping weight (t) | 46.7 | 60.6 | 62.6 | 66.3 | 84 | |
Body dimensions L1*W1*H1 (mm) | 10800×3900×3700 | 12000×4000×3800 | 12600×4100×3800 | 13200×4200×3800 | 13500×4200×4200 | |
Overall dimensions after installation [L2*W2*H2 (mm) | 12900 ×6800 ×5200 | 14800×6800×5300 | 15500 ×6900×6300 | 16000×7000×6300 | 16500 ×9900×7000 | |
Interface diameter (mm) | main steam valve | DN200 | DN200 | DN250 | DN250 | DN250 |
safety valve | DN100+DN100 | 2xDN150 | 2×DN150 | 2×DN150 | 2×DN150 | |
Inlet valve | DN80 | DN80 | DN80 | DN80 | DN80 | |
Drain valve | 2×DN50 | 2×DN50 | 2×DN50 | 2×DN50 | 2×DN50 |
Boiler model | QXS14-1.25/115/70-Q | QXS17.5-1.25/115/70-Q | QXS21-1.25/115/70-Q | QZX29-1.6/130/70-Q | |
Rated thermal power (MW) | 14 | 17.5 | 21 | 29 | |
Rated working pressure (MPa) | 1.25 | 1.25 | 1.25 | 1.6 | |
Rated outlet water temperature (℃) | 115 | 115 | 115 | 130 | |
Rated return water temperature (℃) | 70 | 70 | 70 | 70 | |
Full water capacity (m³) | 16.7 | 18.9 | 23.2 | 25.6 | |
Design thermal efficiency (%) | ≥96 | ≥96 | ≥96 | ≥96 | |
Exhaust smoke temperature (℃) | ≤90 | ≤90 | ≤90 | ≤90 | |
design fuel | Natural gas, city gas, gas, coke oven gas, 0# light diesel oil, etc. | ||||
Maximum shipping weight (t) | 43.6 | 46.8 | 59.8 | 73.2 | |
Body dimensions L1*W1*H1 (mm) | 9000×3800×3300 | 10400×3900×3400 | 11500×4000×3500 | 12700×4200×3600 | |
Overall dimensions after installation L2*W2*H2 (mm) | 11000×6600×4900 | 12500×6800×5000 | 14300×6800×5000 | 15500×7000×6000 | |
Interface diameter (mm) | Outlet valve | DN250 | DN250 | 2×DN200 | 2×DN200 |
Return valve | DN250 | DN250 | DN300 | DN300 | |
safety valve | 2xDN100 | DN100+DN150 | 2×DN150 | 2×DN150 | |
Drain valve | 2×DN50 | 2×DN50 | 2×DN50 | 2×DN50 |
*The above data are for reference only. For specific information, please refer to the actual product and product manual. Unless otherwise specified, the right to interpret the data involved in this website belongs to DABONN.